M88950 MODBUS Register Map
Communication Setting : Baud Rate=57600 (Settable), Parity=None (Settable), Data Bit=8, Stop Bit=1
Function 03 : Data Read , Function 06 : Data Write
Sr. No. |
Parameters |
Function |
Register Numbers |
Values |
CH-1 |
CH-2 |
CH-3 |
CH-4 |
|
|
|
|
|
|
|
|
1 |
Relay Delay |
03/06 |
0 |
1 |
2 |
3 |
0 to 250 Seconds |
|
|
|
|
|
|
|
|
2 |
Relay Hysterisis |
03/06 |
4 |
5 |
6 |
7 |
-10 to 10 |
|
|
|
|
|
|
|
|
3 |
Relay Logic |
03/06 |
8 |
9 |
10 |
11 |
Fail Safe=0, Non Fail Safe=1, Off=2 |
|
|
|
|
|
|
|
|
4 |
Relay Latching Yes or NO |
03/06 |
14 |
15 |
16 |
17 |
Latching Yes=0 , Latching No=1 |
|
|
|
|
|
|
|
|
5 |
Alarm Set Point |
03/06 |
18 |
19 |
20 |
21 |
-999 to 9999 |
|
|
|
|
|
|
|
|
6 |
Trip Set Point |
03/06 |
22 |
23 |
24 |
25 |
-999 to 9999 |
|
|
|
|
|
|
|
|
7 |
Range Low |
03/06 |
26 |
27 |
28 |
29 |
-999 to 9999 |
|
|
|
|
|
|
|
|
8 |
Range High |
03/06 |
30 |
31 |
32 |
33 |
0-9999 |
|
|
|
|
|
|
|
|
9 |
Sensor Select |
03/06 |
38 |
39 |
40 |
41 |
RTD=0, RTD.1=1 |
|
|
|
|
|
|
|
|
10 |
Unit Selection |
03/06 |
42 |
43 |
44 |
45 |
C=0, F=1 |
|
|
|
|
|
|
|
|
11 |
4 mA Output Counts |
03/06 |
46 |
47 |
48 |
49 |
|
|
|
|
|
|
|
|
|
12 |
20 mA Output Counts |
03/06 |
50 |
51 |
52 |
53 |
|
|
|
|
|
|
|
|
|
13 |
PRG COPY FROM (CH-A) |
03/06 |
55 |
|
|
|
CH-B=0, CH-C=1, CH-D=2, None=3 |
|
|
|
|
|
|
|
|
14 |
PRG COPY FROM (CH-B) |
|
56 |
|
|
|
CH-A=0, CH-C=1, CH-D=2, None=3 |
|
|
|
|
|
|
|
|
15 |
PRG COPY FROM (CH-C) |
|
57 |
|
|
|
CH-A=0, CH-B=1, CH-D=2, None=3 |
|
|
|
|
|
|
|
|
16 |
PRG COPY FROM (CH-D) |
|
58 |
|
|
|
CH-A=0, CH-B=1, CH-C=2, None=3 |
|
|
|
|
|
|
|
|
17 |
IPC |
03/06 |
60 |
61 |
62 |
63 |
Input Error Correction |
|
|
|
|
|
|
|
|
18 |
Process Value |
03 |
64 |
65 |
66 |
67 |
Process Value |