MODBUS Register Map of IRD8800 Speed Module M88900
Below is the MODBUS Register Map of IRD8800 Speed module M88900
Register | Datatype | Function | Description |
Channel 1 |
1 | Long Inverse | R/W | TR Set |
2 |
3 | Int | R/W | Hystersis |
4 | Int | R/W | Logic |
5 | Int | R/W | Latch |
6 | Int | R/W | Delay |
7 | Long Inverse | R/W | Alarm Set |
8 |
9 | Int | R/W | Hystersis |
10 | Int | R/W | Logic |
11 | Int | R/W | Latch |
12 | Int | R/W | Delay |
13 | Long Inverse | R/W | Range Hi |
14 |
15 | Int | R/W | Teeth |
16 | Int | R/W | Gap Lo |
17 | Int | R/W | Gap Hi |
18 | Int | R/W | Start timer status |
19 | Int | R/W | Start time |
20 | Int | R/W | curr adjustment |
Channel 2 |
21 | Long Inverse | R/W | TR Set |
22 |
23 | Int | R/W | Hystersis |
24 | Int | R/W | Logic |
25 | Int | R/W | Latch |
26 | Int | R/W | Delay |
27 | Long Inverse | R/W | Alarm Set |
28 |
29 | Int | R/W | Hystersis |
30 | Int | R/W | Logic |
31 | Int | R/W | Latch |
32 | Int | R/W | Delay |
33 | Long Inverse | R/W | Range Hi |
34 |
35 | Int | R/W | Teeth |
36 | Int | R/W | Gap Lo |
37 | Int | R/W | Gap Hi |
38 | Int | R/W | Start timer status |
39 | Int | R/W | Start time |
40 | Int | R/W | curr adjustment |
System |
41 | Long Inverse | R | Channel 1 PV |
42 |
43 | Long Inverse | R | Channel 2 PV |
44 |
45 | Int | R | Channel 1 Tx |
46 | Int | R | Channel 2 Tx |
47 | Int | R | Relay Flags |
48 | Int | R | Status |
49 | Int | R | Unit Number |
50 | Int | R | No. of Channel |
51 | Int | R | Trip Bypass |
52 | Int | R | Bargraph |
53 | Int | R | Baudrate |
54 | Int | R | Parity |
55 | Int | R | 900 |
Related Articles
M88950 MODBUS Register Map
Communication Setting : Baud Rate=57600 (Settable), Parity=None (Settable), Data Bit=8, Stop Bit=1 Function 03 : Data Read , Function 06 : Data Write Sr. No. Parameters Function Register Numbers Values CH-1 CH-2 CH-3 CH-4 1 Relay Delay 03/06 0 1 2 3 ...
IRD8800 MODBUS Output Register Map
Attached you will find the MODBUS RTU/MODBUS TCP/IP Register Map for Cards of the Vibration Monitoring System IRD8800. This register map applied to all cards i.e M88200, M88210, M88250 and M88280
User Manual of IRD6600 (Entek IRD 6600)
IRD6600 is a now Obsolete system that has been replaced by IRD8800. User manual of IRD6600 is attached to this Article.
Performing Write Options on MODBUS Registers remotely on M88200 Modules
IRD8800 Series API670 Compliant Machinery Protection System (MPS) module M88200 is meant for Casing Vibration Measurement. It is a fully programmable module for aspects such as Sensitivity, Full Scale, Measuring Units, Alarm and Trip Set points, ...
Typical Connection Drawing for IRD7100 with MODBUS Output for Casing Vibration
Attached Drawing shows how 2 x Vibration Sensors are connected typically to IRD7100 Machinery Protection Transmitter (MPT) having MODBUS Output