M88200 Casing Vibration
Data Sheet of IRD8800 Series Module M88200-DC for Casing Vibration
IRD8800 Series is an API 670 Compliant Machinery Protection System (MPS). It's module M88200-DC is meant for Casing Vibration measurement. Important aspects of the module are: Sr. No. Characteristic Value 1. Type Electronic Microprocessor based ...
What is the Maximum Current Consumption (Power Consumption) of each Module of IRD8800 Series?
IRD8800 Series is a line of API670 Compliant Machinery Protection System (MPS) manufactured by IRD Mechanalysis Limited in India. Each module of IRD8800 series is designed to perform a specific set of measurement like Casing Vibration, Shaft ...
What is Trip Bypass in IRD8800 Series Modules?
IRD8800 Series is a API670 Compliant Machinery Protection System (MPS). All its modules are equipped with the facility to Bypass Tripping function of the module. By default - Trip Bypass is disabled. However, if User enables Trip Bypass by entering ...
Factory Default Settings applied to Module M88200 of IRD8800 Series
IRD8800 series is a API670 Compliant Machinery Protection System (MPS). It's module M88200 is meant for Casing Vibration measurement. Although the module is fully programmable for units, range, alarm, trip, etc. - for user convenience, each M88200 ...
Performing Write Options on MODBUS Registers remotely on M88200 Modules
IRD8800 Series API670 Compliant Machinery Protection System (MPS) module M88200 is meant for Casing Vibration Measurement. It is a fully programmable module for aspects such as Sensitivity, Full Scale, Measuring Units, Alarm and Trip Set points, ...
4-20 mA output in IRD8800 Series Modules
IRD8800 Series Modules provide a 4-20 mA DC Output proportional to set full scale range (programmable via front panel). 4 mA corresponds to 0 of the Full Scale and 20 mA corresponds to Full Scale Vibration. The Optically Isolated 4-20 mA output for ...
What does the NEXT button on Module M88200 (Casing Vibration) do in IRD8800 Series?
This video showcases the different screens that are available on pressing NEXT button on IRD8800 Series Module M88200 (Casing Vibration Module) By default M88200 shows the Instantaneous Vibration Levels. On long press of Next button on Keypad - it ...
What is the purpose of Captive Screw in Modules of IRD8800 Series?
4 Numbers of Captive Screws are provided per Module in IRD8800 Series systems. They serve the following purpose: They provide means to mechanically secure the modules to the Rack. They provide Electrical and Electronic earth to the modules via the ...
Tx Fail Relay Contacts in IRD8800 Series Monitoring System
IRD8800 Series Monitoring System is designed to provide Tx Fail Relay Contacts per Module in the event of Transducer Failure (Sensor going bad or fault in cable). These contacts can be used for Annunciation. The TX Fail Relay operates when any ...
IRD8800 as replacement for IRD5915
IRD Mechanalysis had a Vibration Monitoring System called IRD5915 in the 20th Century. IRD5915 is now obsolete and is succeeded by our 21st Century Vibration Monitoring System IRD8800. Attached is a drawing which shows how IRD8800 can fit in a cut ...
Firmware Versions of IRD8800 Series Modules M88200, M88210, M88250, M88280, M88300 and M88950
The Firmware Versions in use for IRD8800 Series Modules as on the date of this article are: Module Type Microcontroller Make Firmware Version M88200 Cypress V-1.1.5, 1/10/10 M88200 Microchip V-1.1.7, 26/05/2016 M88210 Microchip V-1.1.0, 2/6/16 M88250 ...
IRD8800 Module M88300 Menu Structure
Attached to this article is the menu structure of Module M88300 of IRD8800 Series
Sensitivity Setting in IRD8800 module M88200
Module M88200 of IRD8800 series allows Sensitivity setting in mV/g and mV/mm/sec. When Sensitivity Unit is set to mV/g, then the card allows setting a sensitivity value between 000.0 and 999.9 mV/g. Typically, the factory set value is kept at 100.0 ...
Typical Backplane Connections for IRD8800
This article lists how connections can be made on Backplane Terminals for IRD8800 - various modules When using IRD8800 Module M88200 with Contact Type Vibration Sensor (IRD521 (Accelerometer) or IRD531 (Velometer), refer the drawing present at this ...
Sensitivity options in IRD8800 Module M88210
The Relative Shaft Vibration Module M88210 of IRD8800 Series allows different Sensitivity options to accommodate different Eddy Current Probes of different manufacturers keeping different Sensitivities. The option to minutely adjust sensitivity also ...
Pre-Commissioning Checklist for IRD8800 Generator End Winding Vibration Monitoring System (GEWVMS)/Stator End Winding Vibration Monitoring System (SEWVMS)
Before IRD8800 for Generator End Winding Vibration Monitoring can be commissioned, the following needs to be ensured by Purchaser at site: Sensors within the Generator (Turbine End and Exciter End) have been mounted and their output has been brought ...
User Manual of Generator End Winding Vibration Monitoring System Card M88280 of IRD8800 Series
Attached to this Article is the User Manual of Generator End Winding Vibration Monitoring System (GEWVMS) Card M88280 of IRD8800 Series
M88250 Recalibration Procedure
The below steps are for calibration in mm/sec pk for Module M88250. The same steps can be repeated by changing display units to mm/sec RMS or microns pk-pk or microns pk. Pre-Requisites Function Generator with Ability to generate Sine Wave (choose an ...
Sensitivity of M88280
M88280 Module of IRD8800 Series is meant for Vibration Monitoring of Generator End Winding. The sensitivity of the module can be adjusted based on the input high temperature sensor and Charge Amplifier. The Sensitivity for a Charge Amplifier with an ...
Calibration Check Table for IRD8800 Series Module M88210
Pre-requisites If you wish to check the Calibration of IRD8800 Series Module M88210, then you would need the following tools: A Signal Generator with the capability to generate a Sine Wave of a fixed frequency and fixed amplitude and an accuracy of ...
User Manual of M88200 of IRD8800 Series
The User Manual of Module M88200 of IRD8800 Series is attached to this article and can be printed or downloaded from here
Calibration Check Table for IRD8800 Series Module M88200
Pre-requisites If you wish to check the Calibration of IRD8800 Series Module M88200, then you would need the following tools: A Signal Generator with the capability to generate a Sine Wave of a fixed frequency and fixed amplitude and an accuracy of ...
Which Type Tests has IRD8800 passed?
IRD8800 is our flagship Vibration Monitoring System and is API 670 Compliant. The series has been type tested for the following tests in which it has passed and the results are current: Dry Heat Cyclic, IS:9000 P-III Damp Heat Cyclic, IS: 9000 P-V ...
IRD8800 MODBUS Output Register Map
Attached you will find the MODBUS RTU/MODBUS TCP/IP Register Map for Cards of the Vibration Monitoring System IRD8800. This register map applied to all cards i.e M88200, M88210, M88250 and M88280
What is the purpose of key phasor module in vibration monitoring system? Can it be used to extract balancing data?
The purpose of the Key Phasor module in a Vibration Monitoring System is to act as the reference point for phase on a machine train. Using this reference point, the vibration phase of other sensors on the machine train can be deduced. Usually the ...