Introduction
This Article serves as the User Manual when IRD8800 is used for Temperature Monitoring
Introduction to IRD Mechanalysis Limited
IRD Mechanalysis Limited - also commonly referred to as 'IRD' - is a provider of Condition Monitoring Solutions to the World since 1962. IRD provides Portable Instruments and Online Systems for Vibration, Temperature, Gap, Speed and Turbine Monitoring. IRD also provides associated services like Training, Consulting, Commissioning, Repairs and Calibration
Introduction to Temperature Monitoring
Temperature Monitoring is the practice of using Temperature Sensors like IRD515 (Vibration cum Temperature) or PT-100 RTD to continuously monitor Temperature of Industrial Machinery like Motors, Fans, Pumps, Compressors and more. This helps the user in Predictive Maintenance. The user is able to Monitor Temperature and get early warnings. The user is also able to protect their machine in event of Higher than acceptable temperatures
Introduction to IRD8800
IRD8800 Series of Monitoring System made by IRD in India is a Rack Based API670 Compliant Machinery Protection System (MPS). It has Modules for Vibration, Temperature, Speed, Gap and Turbine Monitoring
Temperature Monitoring Module M88950
M88950 is a 4 Channel Module. It can accept Input from 4 Numbers of RTD PT-100
Full Scale Range
M88950 can Monitor Temperature in both Degrees Celsius as well as Degrees Fahrenheit. The Full Scale can be set to any value between the minimum and maximum permissible range. The Range is -100 Deg C to +500 Deg C when measuring in Degrees Celsius. The Range is -100 Deg F to +932 Deg F when measuring in Degrees Fahrenheit
4-20mA Output
M88950 provides Galvanically Isolated 4-20mA output proportional to set Full Scale Range. For example - if Full Scale range is -20 Deg C to +400 Deg C - then the module will provide 4mA output when reading is -20 Deg C and 20mA ouput when reading is +400 Deg C
Below Range and Over Range
If measured temperature goes below Range - then M88950 displays IPLO for the particular channel denoting Input Low and it brings the 4-20 mA output to 2.8 mA for indicating false signal to DCS/PLC/SCADA. If measured temperature goes Over Range - then M88950 displays IPHI for the particular channel denoting Input High and it brings the 4-20 mA output to 2.8 mA for indicating false signal to DCS/PLC/SCADA
M88950 has a Relay that has Independent Potential Free, 2 sets of Contacts per Channel rated for 5A
@230 V AC resistive
MODBUS Output
RS485 MODBUS RTU Output; Default 57600 Baud Rate; Parity: None