Factory Default Settings applied to Module M88200 of IRD8800 Series
IRD8800 series is a API670 Compliant Machinery Protection System (MPS). It's module M88200 is meant for Casing Vibration measurement. Although the module is fully programmable for units, range, alarm, trip, etc. - for user convenience, each M88200 module is set to following factory default settings. The user can alter these settings as per their requirement.
- Password: 0000
- Change Password: No
- Module Address: 001
- Baud Rate: 9600
- Parity: None
- No. of Channels: 2
- Trip Bypass: No
- Bar Graph % of: FS Range Set
- Channel A Prog: Yes
- A Sns Units? : Based on order Requirement either mV/g or mV/mm/s
- A Sns: Based on sensor selection either 100.0 mV/g or 4.000 mV/mm/s
- A Unit: mm/s RMS
- A-FS mm/s RMS : 50.0 mm/s RMS
- A- Floor Noise % : 00
- A- TX Fail HI : 30.0 V
- A- TX Fail LO : 00.0V
- A- Filter: In
- A- Filter LP : 1 KHz
- A- Filter HP: 10 Hz
- A- Start up: Enable
- A- Start up Delay: 001 Min
- A- Adj 4mA: Adjusting the counts while observing 4.03 mA DC on Multimeter
- A- Trip Set: 80% of Full Scale Selected (040.0 mm/s RMS)
- A- Tr Hysterisys: 00
- A- Tr FS/NFS: Non Fail Safe
- A- Tr Latching : Disabled
- A- Tr Delay: 05 Sec
- A- Alarm Set: 60% of Full Scale Selected (030.0 mm/s RMS)
- A -Al Hysterisys: 00
- A- AL FS/NFS: Non Fail Safe
- A- AL Latching : Disabled
- A- AL Delay: 03 Sec
- Channel B Prog: Yes
- Copy Ch A Prog : Yes
So, Channel A and Channel B are given the same default settings.