Factory Default Settings applied to Module M88200 of IRD8800 Series

Factory Default Settings applied to Module M88200 of IRD8800 Series

IRD8800 series is a API670 Compliant Machinery Protection System (MPS). It's module M88200 is meant for Casing Vibration measurement. Although the module is fully programmable for units, range, alarm, trip, etc. - for user convenience, each M88200 module is set to following factory default settings. The user can alter these settings as per their requirement.
  1. Password: 0000
  2. Change Password: No
  3. Module Address: 001
  4. Baud Rate: 9600
  5. Parity: None
  6. No. of Channels: 2
  7. Trip Bypass: No
  8. Bar Graph % of: FS Range Set
  9. Channel A Prog: Yes
  10. A Sns Units? : Based on order Requirement either mV/g or mV/mm/s
  11. A Sns: Based on sensor selection either 100.0 mV/g or 4.000 mV/mm/s
  12. A Unit: mm/s RMS
  13. A-FS mm/s RMS : 50.0 mm/s RMS
  14. A- Floor Noise % : 00
  15. A- TX Fail HI : 30.0 V
  16. A- TX Fail LO : 00.0V
  17. A- Filter: In
  18. A- Filter LP : 1 KHz
  19. A- Filter HP: 10 Hz
  20. A- Start up: Enable
  21. A- Start up Delay: 001 Min
  22. A- Adj 4mA: Adjusting the counts while observing 4.03 mA DC on Multimeter
  23. A- Trip Set: 80% of Full Scale Selected (040.0 mm/s RMS)
  24. A- Tr Hysterisys: 00
  25. A- Tr FS/NFS: Non Fail Safe
  26. A- Tr Latching : Disabled
  27. A- Tr Delay: 05 Sec
  28. A- Alarm Set: 60% of Full Scale Selected (030.0 mm/s RMS)
  29. A -Al Hysterisys: 00
  30. A- AL FS/NFS: Non Fail Safe
  31. A- AL Latching : Disabled
  32. A- AL Delay: 03 Sec
  33. Channel B Prog: Yes
  34. Copy Ch A Prog : Yes
So, Channel A and Channel B are given the same default settings.